Description:
LKM 262 The digital programmable measurement converter LKM 262 is a digital programmable measurement converter suitable for installation on standard rails. This converter is programmable and suitable for different thermocouples, complying with DIN EN 60584-3 standard. LKM 262 linearly converts the temperature dependent thermoelectric voltage of the sensor into a standard signal. Signal range: 0 to 10V. Temperature compensation is effective within the measurement converter itself. The measurement converter can be programmed using the universal interface LKM S1 provided by RS. Adjusting the controller allows for immediate small display corrections. Input: Thermocouples K, J, L, T, U, E, N, S, B, R, C (within the corresponding defined range) Zero: -200 to 600 ° C *, depending on thermocouple range: 50 K Linear error: 0.3K, depending on thermocouple measurement error: 0.2% Reference contact error:+/-0.5 ° C Power supply voltage: 15 to 35V DC, 15 to 26V AC, polarity reversal protection Maximum current consumption: 20mA Output: 0 to 10V, programmable sensor fault: 10V Short circuit: Voltage value at room temperature Response time: 0.5s TC: 100ppm/° C Operating temperature range: -40 to 85 ° C Humidity: 95% Installation: 35mm DIN rail Shell: Polycarbonate 75x25x53mm Terminal Type: Screw Terminal Clamping Range: 0.2 to 2.5mm ² Weight: Approximately 60g Vibration: 5g/10 to 200Hz # # # Note LKM S1 universal interface, please refer to RS Inventory Number 9130857 # # # Recognized EMC Radiation and Noise Resistance: EN 61326-1:2006 EN 61326-2-3:2006 # # Temperature Transformer